4–20 mA Analog Input Design: Burden Resistor, Protection, Isolation and ADC Scaling
4–20 mA Analog Input Design: Burden Resistor, Protection, Isolation and ADC Scaling
4–20 mA is widely used in industrial instrumentation because current transmission is less sensitive than voltage transmission to cable resistance and ground-potential differences. The receiver still has to convert the loop current into a voltage that an ADC can measure. The key design decisions are the burden resistor, loop-voltage budget, input protection, filtering, isolation and ADC interface.

1. Calculate the burden resistor
The conversion follows V = I × R. A 120 Ω burden produces 0.48 V at 4 mA and 2.40 V at 20 mA. Its dissipation at 20 mA is I²R = 0.048 W. A 250 Ω burden produces 1–5 V and dissipates 0.10 W at 20 mA. The larger resistor creates a larger signal but consumes more loop compliance voltage. Choose the value from the ADC range and the complete transmitter/cable voltage budget, not from resolution alone.
| Burden | 4 mA output | 20 mA output | Power at 20 mA | Design note |
|---|---|---|---|---|
| 120 Ω | 0.48 V | 2.40 V | 48 mW | Useful for a 2.5 V-class ADC range with headroom. |
| 150 Ω | 0.60 V | 3.00 V | 60 mW | May suit a 3.3 V input range after tolerance review. |
| 250 Ω | 1.00 V | 5.00 V | 100 mW | Common 1–5 V conversion, but needs adequate loop voltage. |
Apply resistor power derating for ambient temperature and fault current. Precision designs should consider tolerance and temperature coefficient, but total error also includes ADC reference, amplifier offset and gain, leakage, PCB contamination and calibration. The loop supply must cover transmitter minimum operating voltage, cable drop, burden voltage and protection/barrier drops at maximum current.
2. Protect the field input
Industrial terminals may see reverse wiring, ESD and surge transients. A front end may include a series current-limiting element, TVS or clamp network, reverse-polarity protection and a defined return path. Select the TVS for working voltage, clamp voltage, surge waveform, capacitance and leakage at temperature. Leakage current through a protection device can become a measurable offset, especially near the 4 mA low end.

3. Choose the RC filter from bandwidth
A first-order low-pass filter has fc = 1 / (2πRC). With 1 kΩ and 100 nF, fc is about 1.59 kHz; with 1 kΩ and 1 µF, it is about 159 Hz. A lower cutoff rejects more noise but increases settling time. If HART communication is required, preserve the 1200 Hz and 2200 Hz FSK components; an aggressive low-pass filter can attenuate the communication signal. Also check ADC sampling-capacitor settling through the source impedance. A buffer may be required.
4. Decide on channel isolation
Isolation is useful when field wiring and controller grounds can differ, when channels must not share ground-loop current, or when the product safety architecture requires a barrier. Treat the signal isolator and isolated DC/DC supply as one system. Check working voltage, transient rating, creepage and clearance against the applicable product standard. Do not infer an isolation rating from the component package alone.
5. Validate the whole signal chain
| Test | What to verify | Record |
|---|---|---|
| Zero/full scale | 4 mA and 20 mA conversion, headroom and linearity. | Measured values and calibration coefficients. |
| Intermediate points | 8, 12 and 16 mA response. | Current-to-ADC-code table. |
| Fault wiring | Open loop, reverse wiring and recovery. | Fault thresholds and recovery behavior. |
| Noise/filter | Ripple, settling and injected interference. | Scope captures and bandwidth settings. |
| Isolation/surge | Performance against the defined test plan. | Test report and acceptance criteria. |
A reliable 4–20 mA receiver is more than a resistor and an ADC pin. The loop budget, protection leakage, filter response, reference accuracy, isolation and calibration must be engineered together.