Home > Electronics & Hardware Design > The differential voltage is normal – why is the RS485 signal still distorted?

The differential voltage is normal – why is the RS485 signal still distorted?

Views: 94 Publish Time: 2026-08-27 16:55:17

01.png

The oscilloscope's mathematical channel shows that the amplitude of A – B is normal; however, the RS485 receiver still exhibits bit errors or output distortion. Do not focus solely on the differential value: the prerequisite for the receiver to correctly compare A and B is that the potentials at the two input pins relative to the local ground remain within the allowable common-mode range. A potential difference between the two ground terminals can cause both A and B to drift simultaneously; even though the differential signal remains unchanged, the input stage may have already exceeded its operating limits.

A long transmission line exhibited stable communication on the test bench; however, upon connecting it to a remote cabinet, random bit errors began to occur. When measuring the A–B signal, the differential amplitude and edge characteristics appeared clearly distinguishable; changing the baud rate only provided a slight mitigation of the issue. This phenomenon might lead one to continue adjusting the terminal resistor, but if independent power supplies are used at both ends, the waveform that actually needs to be compensated for in the first group is actually the signal from A to the receiver ground and from B to the receiver ground.

01 Fault Point 1: Differential reception also requires a common-mode window

The RS485 receiver output is determined by the difference between inputs A and B; however, the internal input transistor is not operating within an infinite voltage range. The data sheet specifies the allowable common-mode input range, and the specification also requires the receiver to perform its decision-making operation within this defined range. As long as inputs A and B are shifted together and remain within the specified window, the differential decision-making can be maintained; once the boundary is exceeded, the linear input stage, protection circuitry, or bias network may no longer operate under normal conditions.

02.png

The differential voltage is superimposed on the common-mode voltage; thus, the receiver is subject to the constraints imposed by both voltages simultaneously. Source: RS-422 and RS-485 Applications Ebook.

For example, when the remote ground potential is higher than the local ground potential by a certain amount, the A and B signals output by the driver are perfectly normal relative to the remote ground; however, upon reaching the local receiver, both lines are raised simultaneously. The difference between A and B may still remain at its original value, but the A–B voltage relative to the local ground has now approached or even exceeded the device's operating range. In this case, the reverse ground potential difference will pull both lines downward simultaneously.

02 Fault Point 2: The third reference line is not the universal ground wire.

Many RS485 cables include not only twisted-pair conductors but also a signal reference conductor. This conductor is used to establish a controllable common-mode reference between the transmitter and receiver, rather than serving as a protective ground, shielding layer, or means of carrying high currents. If the reference conductor is thin and long, or if its connection to the equipment ground is unclear, its inherent voltage drop and loop current can still generate a ground potential difference.

Directly hard-wiring the chassis ground, signal ground, and shielding layer together may introduce power-frequency ground loop currents or transient currents. The selection of this approach should be based on the power supply topology, grounding system, cable length, and surge environment. When the ground potential difference is uncontrollable, an isolated transceiver separates the logic-side and bus-side reference planes – a solution that is often more effective than simply relaxing the grounding requirements.

03.png

The isolated RS485 bus transceiver separates the bus-side transceiver from the local logic reference, reducing the risk of a ground potential difference directly affecting the input stage. Source: RS-422 and RS-485 Applications Ebook.

03 Fault Point 3: Terminal and Bias issues can only resolve another category of problems.

The terminal resistor is used to match the transmission line impedance and reduce reflections; the fail-safe bias is employed to establish a well-defined differential state when the bus is not driven. Neither of these measures automatically expands the receiver's common-mode range. If the differential waveform exhibits ringing, the terminal resistance should be checked; if there is idle-state drift, the bias value should be checked; if the A–B signal exceeds the local ground boundary, reference, isolation, and protection paths must be addressed.

TVS also has similar boundaries. Clamping each wire to the local ground can help limit transient voltages; however, device capacitance, clamping voltage, and return-path impedance can affect both the signal and the common-mode behavior. If the local ground itself experiences a sharp spike during a transient event, the turn-on of the protection device does not necessarily mean that the receiving chip's pin is safe. The layout should ensure that the surge current returns to the port reference as quickly as possible, rather than flowing through the logic ground before finding an exit.

04.png

The specification sheet also specifies the receiver's differential threshold and common-mode operating conditions; neither can be selected for viewing independently. Source: RS-422 and RS-485 Applications Ebook.

04 Extend the measurement from one curve to three curves

1. Use a differential probe or mathematical channel to record A–B data, and verify the valid differential amplitude, reflection, and edge conditions.

2. Record the local location of Receiver A and the local location of Receiver B, along with their idle and communication states.

3. Directly measure the DC and low-frequency potential difference between the two signal references and observe any changes in the load.

4. Compare the measured operating range with the common-mode, absolute maximum ratings, and protection conditions specified in the relevant transceiver data sheet.

5. If isolation is employed, continue to verify the power supply on the isolated side, isolation withstand voltage, common-mode transient capability, and shielding return current.

05.png

The receiver should simultaneously mark the path with a differential threshold, a common-mode window, and a local reference point.

The measurement reference point must be clearly specified. The statement "A is 3V" does not indicate which ground reference it is relative to; thus, the information is incomplete. Additionally, it is essential to verify that the common-mode input range of the differential probe is sufficient. When using two standard single-ended probes for subtraction measurement, the oscilloscope's protective ground may inadvertently connect the two systems together, which could both alter the fault diagnosis and pose a safety risk.

If a fault occurs only after certain nodes are connected, verify whether the transceiver models are identical; the input common-mode range, failure protection threshold, input resistance, and shutdown state may vary across different devices. When a powered-down node loads the bus via a protection structure or bias network, it may also alter the ground voltage of the two lines – such cases should not be excluded simply because the node is not transmitting data.

On-site recordings should ideally also indicate the receiver's power supply voltage and ground potential variations. If bit errors occur in synchronization with the startup or shutdown of high-power equipment, yet the differential amplitude remains relatively unchanged, then common-mode excursion or ground return current should be suspected; if the bit errors vary with line length or edge velocity, then signal reflection or terminal issues are more likely suspect. Grouping these phenomena according to their underlying mechanisms can help avoid repeated trial and error between terminal, bias, and isolation considerations.

The final conclusion is that the RS485 interface's common-mode immunity has limitations—it cannot be simply ignored just because differential signaling is used. First, capture both the A–B signal and the two ground waveforms simultaneously; then determine whether to configure the terminal, reference line, implement isolation, or apply port protection. When troubleshooting long-distance RS485 connections, does the oscilloscope typically only record the A–B voltage difference, or does it simultaneously record the voltages at both the A and B terminals relative to the local ground at the receiving end?

About the Author

Zheng Zhenyu图片6.png

Director of FanYi; Former Invited Lecturer at Altium; Senior Lecturer at FanYi Education; Expert Member of the Expert Pool for the "Electronic Information Talent Capacity Enhancement Project" organized by the Chinese Institute of Electronics; Currently serves as General Manager of FanYi Education; He has long been dedicated to the application of Altium Designer high-speed PCB design software and possesses extensive practical experience in PCB design techniques for high-speed interconnects, high-speed DDR3/DDR4, EMI, EMC, SI, and PI applications. His published works include "Altium Designer 24 (Chinese Edition): A Practical Guide to Rapid Electronic Design," which has been frequently selected as supplementary material for competitions, internships, and applied courses at various higher education institutions.